Table 8-12
Connections of environment monitoring cables in the F01D1000 cabinet
Cable
One End Connects to...
The Other End
Connects to...
Monitoring cable
(1): J1 port of the sensor
transfer box
(1): DB50 port on the
monitoring unit of the
ETP4890
Test and alarm cable
l
(2.2): JTD1 port of the
sensor transfer box
l
(2.3-2.4): RS485/RS232
or COM ports on the
monitoring unit of the
ETP4890
l
(2.1): STACK IN port on
the HWTF transfer
board of the HABF
extended shelf
(2): STACK OUT port on
the HWCF transfer board
of the HABD master shelf
Test and alarm subtending cable (3): JTD2 port of the sensor
transfer box
(3): STACK OUT port on
the HWTF transfer board
of the HABF shelf
Test and alarm subtending cable (7): JTP3 port of the sensor
transfer box
(4): STACK OUT port on
the HABD slave shelf of
the right device
compartment
Monitoring cable of the surge
protector
JTP4 port of the sensor
transfer box
Alarm terminal of the
surge protector
Smoke sensor cable
SMOKE port of the sensor
transfer box
Smoke sensor
Monitoring cable of the heat
exchanger
JTP6 port of the sensor
transfer box
Heat exchanger
Door status sensor
communication cable of MDF
compartment
JTP7 port of the sensor
transfer box
MDF compartment door
status sensor
Monitoring cable of the MDF
JTP1 port of the sensor
transfer box
Alarm bar of the MDF
Door status sensor
communication cable of
equipment compartment and
temperature control
compartment
JTM1 port of the sensor
transfer box
Equipment compartment
and temperature control
compartment door status
sensor
Monitoring cable of the
temperature sensor
VTEM2 terminal of the
sensor transfer box
Temperature sensor
Monitoring cable of the battery
temperature sensor
VBTEM2 terminal of the
sensor transfer box
Temperature sensor of the
battery
UA5000 Universal Access Unit
Environment Monitoring
8 ETP4890 Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential