15. Query the alarms, and confirm that the door status alarm other than alarms for other
monitoring parameters is generated.
huawei(config-if-power4875l-0)#
display power alarm
EMU ID: 0 Power alarm information
----------------------------------------------------------------------------
Mains supply yes : Yes Mains supply lack : Normal
Total Vol lack : Normal
Load fuse 0 : Connect Second fuse : Connect
Load off : On Battery off : On
Battery 0 loop : Disconnect
Environment Temperature : Normal Environment Humidity : Normal
Door alarm : Alarm Water alarm : Normal
Fog alarm : Normal Wiring alarm : Normal
Module 0 : Normal
Module 1 : Normal
Module 2 : Normal
Battery temperature off state : Normal Load temperature off state : Normal
----------------------------------------------------------------------------
Name State |Name State
Spare Dig0(Fan) Normal|Spare(HABF_FAN)
Normal
Spare Dig2 Normal|Spare Dig3(SPD)
Normal
Spare Dig4(Smoke) Normal|Spare Dig5(HEX) Alarm
Spare Dig6(MDF-door) Alarm
----------------------------------------------------------------------------
NOTE
The door status sensors of the device compartment and the temperature control compartment are in
serial connection, and are monitored as a variable. These two door status sensors are automatically
configured by the system. The door status alarm is generated because the door is open.
16. Save the data.
huawei(config-if-power4875l-0)#
quit
huawei(config)#
save
17. Close all doors of the cabinet. Then, query the alarm information again, and confirm that
there is no alarm for any monitoring parameter.