Table 9-3
Settings of SW101-1, SW101-2 and SW101-3
SW101-3
SW101-2
SW101-1
Address Bit Value
ON
ON
ON
0
ON
ON
OFF
1
ON
OFF
ON
2
ON
OFF
OFF
3
OFF
ON
ON
4
OFF
ON
OFF
5
OFF
OFF
ON
6
OFF
OFF
OFF
7
Table 9-4
Settings of SW101-5 and SW101-6
SW101-6
SW101-5
Number of Fans
ON
ON
6
ON
OFF
2
OFF
ON
4
OFF
OFF
3
Table 9-5
Settings of SW101-7 and SW101-8
SW101-8
SW101-7
Adjust Speed
According to...
Adjustment Method
ON
ON
Temperature at the air
intake vent
Method 1
ON
OFF
Temperature at the air
exhaust vent
Method 2
OFF
ON
Reserved
Method 3
OFF
OFF
Temperature at the air
intake vent (The fan
stops rotating.)
Method 4
SW201
describes the default settings of DIP switches of SW201.
UA5000 Universal Access Unit
Environment Monitoring
9 Fan Tray Monitoring Solution
Issue 01 (2012-08-17)