COM ID Command BaudRate DataLength StopLength ParityType
0 - - - - -
1 - - - - -
PowerNumber : 0 PowerType : -
----------------------------------------------------------------------------
The results show that certain monitoring parameters, such as temperature, humidity, door
status, and MDF, have been configured automatically in the system. Other monitoring
parameters, however, need to be configured manually.
4.
Configure the analog parameters.
huawei(config-if-h303esc-0)#
esc analog 0 alarm-upper-limit 50 alarm-lower-
limit 10
huawei(config-if-h303esc-0)#
esc analog 1 alarm-upper-limit 80 alarm-lower-
limit 5
huawei(config-if-h303esc-0)#
esc analog 4 alarm-upper-limit 75 alarm-lower-
limit 45 name Supply_Voltage sensor-type 0:voltage analog-alarm 3 unit Volt
5.
Configure the digital parameters.
huawei(config-if-h303esc-0)#
esc digital 2 available-level low-level digital-
alarm 13 name fan1
huawei(config-if-h303esc-0)#
esc digital 3 available-level low-level digital-
alarm 13 name fan2
huawei(config-if-h303esc-0)#
esc digital 4 available-level low-level digital-
alarm 13 name fan3
huawei(config-if-h303esc-0)#
esc digital 5 available-level low-level digital-
alarm 13 name fan4
6.
Query the environment information, and confirm that the environment monitoring
functions are normal and the door status alarm other than alarms for other monitoring
parameters is generated.
huawei(config-if-h303esc-0)#
display esc environment info
EMU ID: 0 ESC environment state
FAN control mode :Auto FAN run state: Open
---------------------------Analog environment info--------------------------
ID Name State Value AlmUpper AlmLower Unit
0 Temperature Normal 29.00 50 10 C
1 Humidity Normal 30.98 80 5 %R.H.
2 - Normal -128.00 127 -128 -
3 - Normal -128.00 127 -128 -
4 Supply_Voltage Normal 53.50 75 45 -
5 Normal -128.00 127 -128 -
6 - Normal -128.00 127 -128 -
7 - Normal -128.00 127 -128 -
---------------------------Digital environment
info---------------------------
ID Name State Value |ID Name State Value
0 Wiring Normal 1 |1 Door0 Alarm 1
2 fan1 Normal 0 |3 fan2 Normal 0
4 fan3 Normal 0 |5 fan4 Normal 0
6 - Normal 1 |7 - Normal 1
8 - Normal 1 |9 - Normal 1
10 - Normal 1 |11 - Normal 1
12 - Normal 1 |13 - Normal 1
14 - Normal 1 |15 - Normal 1
16 - Normal 1 |17 - Normal 1
18 - Normal 1 |19 - Normal 1
20 - Normal 1 |21 - Normal 1
----------------------------------------------------------------------------