To...
Run the Command...
Configure the digital
parameters
esc digital
IDs of user-defined alarms in the digital parameters: IDs 1-20
are reserved alarm IDs in the system (1: AC_voltage; 2:
AC_switch; 3: Battery_voltage; 4: Battery_fuse; 5: Load_fuse;
6: Rectifier; 7: DC_power; 8: Cupboard_door; 9: Room_door;
10: Window; 11: Theft; 12: Wiring; 13: Fan; 14: Fire; 15: Fog;
16: Water; 17: Diesel; 18: Smell 19: Air_conditioner; 20: SPD),
and IDs 21-52 are alarm IDs allocated to other user-defined
alarms by users.
The following considers the configuration in the F02AF cabinet with the C-type PDU as an
example to describe the process of configuring the environment monitoring parameters of the
H304ESC board.
1.
Log in to the UA5000 through the maintenance terminal and add an EMU.
huawei(config)#
emu add 0 H304ESC 0 30 rs232 H304ESC
2.
Query the status of the H304ESC board.
huawei(config)#
display emu 0
EMU ID: 0
----------------------------------------------------------------------------
EMU name : H304ESC
EMU type : H304ESC
Used or not : Used
EMU state : Normal
Frame ID : 0
Subnode : 30
COM port : RS232
----------------------------------------------------------------------------
3.
Enter the H304ESC configuration mode and query the default analog and digital
parameters.
huawei(config)#
interface emu 0
huawei(config-if-h304esc-0)#
display esc system parameter
EMU ID: 0 ESC system parameter
----------------------------------------------------------------------------
FAN run mode: Auto Auto open temperature: 45 C Auto close temperature: 30 C
AnalogID Name AlmUpper AlmLower TestUpper TestLower Unit Type
0 Temperature 55 5 100 -27 C Voltage
1 - 127 -128 127 -128 - Voltage
2 - 127 -128 127 -128 - Voltage
3 - 127 -128 127 -128 - Voltage
4 Supply_Voltage 75 45 100 0 Volt Voltage
5 - 127 -128 127 -128 - Voltage
6 - 127 -128 127 -128 - Voltage
7 - 127 -128 127 -128 - Voltage
----------------------------------------------------------------------------
DigitalID Name Level |DigitalID Name Level
0 Wiring 1 | 1 Door0 0
2 - 1 | 3 - 1
4 - 1 | 5 - 1
6 - 1 | 7 - 1
8 - 1 | 9 - 1
10 - 1 | 11 - 1
12 - 1 | 13 - 1
14 - 1 | 15 - 1
16 - 1 | 17 - 1
18 - 1 | 19 - 1
20 - 1 | 21 - 1
UA5000 Universal Access Unit
Environment Monitoring
4 H304ESC Monitoring Solution