COM ID Command BaudRate DataLength StopLength ParityType
0 - - - - -
1 - - - - -
PowerNumber : 0 PowerType : -
Battery off permission: Permit Battery off voltage: 43.2V
Battery0 capacity: 100A Battery1 capacity: 100A Equalizing time: 60days
----------------------------------------------------------------------------
The results show that certain monitoring parameters, such as temperature, voltage, door
status, and MDF, have been configured automatically in the system. Other monitoring
parameters, however, need to be configured manually.
4.
Configure the analog parameters.
huawei(config-if-h304esc-0)#
esc analog 0 alarm-upper-limit 50 alarm-lower-
limit 5
huawei(config-if-h304esc-0)#
esc analog 5 alarm-upper-limit 80 alarm-lower-
limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH
5.
Configure the digital parameters.
huawei(config-if-h304esc-0)#
esc digital 2 available-level low-level name SPD1
huawei(config-if-h304esc-0)#
esc digital 3 available-level low-level name SPD2
huawei(config-if-h304esc-0)#
esc digital 4 available-level low-level name SW1
huawei(config-if-h304esc-0)#
esc digital 5 available-level low-level name SW2
huawei(config-if-h304esc-0)#
esc digital 6 available-level low-level name SW3
huawei(config-if-h304esc-0)#
esc digital 8 available-level low-level name fan1
huawei(config-if-h304esc-0)#
esc digital 9 available-level low-level name fan2
huawei(config-if-h304esc-0)#
esc digital 10 available-level low-level name fan3
huawei(config-if-h304esc-0)#
esc digital 11 available-level low-level name fan4
6.
Query the environment information, and confirm that the environment monitoring
functions are normal and the door status alarm other than alarms for other monitoring
parameters is generated.
huawei(config-if-h304esc-0)#
display esc environment info
EMU ID: 0 ESC environment state
FAN control mode :Auto FAN run state: Close Battery charge state: Floating
---------------------------Analog environment info--------------------------
ID Name State Value AlmUpper AlmLower Unit
0 Temperature Normal 29.00 55 5 C
1 - Normal 0.00 127 -128 -
2 - Normal 0.00 127 -128 -
3 - Normal -128.00 127 -128 -
4 Supply_Voltage Normal 52.73 75 45 Volt
5 Humidity Normal 30.98 80 0 -
6 - Normal -128.00 127 -128 -
7 - Normal -128.00 127 -128 -
---------------------------Digital environment info
ID Name State Value |ID Name State Value
0 Wiring Normal 1 |1 Door0 Alarm 1
2 SPD1 Normal 0 |3 SPD2 Normal 0
4 SW1 Normal 0 |5 SW2 Normal 0
6 SW3 Normal 0 |7 - Normal 1
8 fan1 Normal 0 |9 fan2 Normal 0
10 fan3 Normal 0 |11 fan4 Normal 0
12 - Normal 1 |13 - Normal 1
14 - Normal 1 |15 - Normal 1
16 - Normal 1 |17 - Normal 1
18 - Normal 1 |19 - Normal 1
20 - Normal 1 |21 - Normal 1
----------------------------------------------------------------------------
NOTE
Door status alarm "Door0" is generated because the door is open. At this time, if you turn on the
buzzer on the front panel of the H304ESC board, the buzzer generates a buzzing tone.
7.
Save the data.
huawei(config-if-h304esc-0)#
quit
huawei(config)#
save
UA5000 Universal Access Unit
Environment Monitoring
4 H304ESC Monitoring Solution
Issue 01 (2012-08-17)