Data Plan
provides the data plan for configuring the ESCM.
Table 5-8
Data plan for configuring the ESCM
Item
Data
Remarks
EMU
Type: ESCM
ESCM is displayed as
ESCM
on the CLI.
SN: 0
-
Subnode ID: 30
The serial port of the ESCM is an RS232
serial port, and the subnode ID must be set to
30.
Analog
parameters
Analog parameter ID: 0
This analog parameter is set according to the
actual requirements. The built-in analog
parameter is set here to monitor the ambient
temperature of the device.
Upper alarm threshold of
analog parameter 0: 50
When the ambient temperature of the device
is equal to or higher than 50°C, the host
reports an alarm.
Default: 55°C.
Lower alarm threshold of
analog parameter 0: 10
When the ambient temperature of the device
is equal to or lower than 10°C, the host
reports an alarm.
Default: 5°C.
Analog parameter ID: 1
This analog parameter is set according to the
actual requirements. The built-in analog
parameter is set here to monitor the voltage
of the device.
Upper alarm threshold of
analog parameter 1: 75 V
When the voltage of the device is equal to or
lower than -75V, the host reports an alarm.
Default: -75V.
Lower alarm threshold of
analog parameter 1: 45 V
When the voltage of the device is equal to or
lower than -45 V, the host reports an alarm.
Default: -45 V.
Analog parameter ID: 2
The user-defined humidity monitoring
analog parameter is added to monitor the
humidity of the device.
Upper alarm threshold of
analog parameter 2: 80
When the humidity of the device is equal to
or lower than 80% RH, the host reports an
alarm.
Lower alarm threshold of
analog parameter 2: 0
When the humidity of the device is equal to
or lower than 0% RH, the host reports an
alarm.
UA5000 Universal Access Unit
Environment Monitoring
5 ESCM Monitoring Solution