Item
Data
Remarks
Name of analog parameter
2: Humidity
-
Alarm ID of analog
parameter 2: 2
The user-defined humidity alarm of the
system is used.
Unit of analog parameter 2:
% RH
-
Sensor type of analog
parameter 2: voltage type
-
Digital
parameters
Digital parameter ID: 0
The monitoring digital parameter of the
MDF sensor is set here to monitor the status
of the MDF. When the MDF is faulty, the
host reports an alarm.
Allocated by default (unable to be changed
by the user).
Valid level of digital
parameter 0: high level
When the high level represents the valid
level, the host does not report an alarm in the
case of high level.
Digital parameter ID: 1
The monitoring digital parameter of the door
status sensor is set here to monitor the door
status. When the cabinet door is opened, the
host reports an alarm.
Allocated by default (unable to be changed
by the user).
Valid level of digital
parameter 1: low level
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
Digital parameter ID: 9
The user-defined water monitoring analog
parameter is added.
Valid level of digital
parameter 9: low level
When the low level represents the valid level,
the host does not report an alarm in the case
of low level.
NOTE
The preceding data is configured according to the actual requirements. When the actually planned value
of a parameter is the same as the default value, it is not necessary to configure the parameter.
Configuration Process
The monitoring parameters can be reported to the control board only when the data of the ESCM
is correctly configured in the system.
shows the configuration process, and
lists the commands used during the configuration.