To...
Run the Command...
Configure the digital parameters
esc digital
IDs of user-defined alarms in the digital parameters: IDs
1-20 are reserved alarm IDs in the system (1:
AC_voltage; 2: AC_switch; 3: Battery_voltage; 4:
Battery_fuse; 5: Load_fuse; 6: Rectifier; 7: DC_power;
8: Cupboard_door; 9: Room_door; 10: Window; 11:
Theft; 12: Wiring; 13: Fan; 14: Fire; 15: Fog; 16: Water;
17: Diesel; 18: Smell 19: Air_conditioner; 20: SPD), and
IDs 21-52 are alarm IDs allocated to other user-defined
alarms by users.
The following considers the configuration in the M200 cabinet as an example to describe the
process of configuring the environment monitoring parameters of the ESCM.
1.
Log in to the UA5000 through the maintenance terminal and add an EMU.
huawei(config)#
emu add 0 MiniESC 0 30 rs232 MiniESC
2.
Enter the ESCM configuration mode and query the default analog and digital parameters.
huawei(config)#
display emu 0
EMU ID: 0
----------------------------------------------------------------------------
EMU name : MiniESC
EMU type : MiniESC
Used or not : Used
EMU state : Normal
Frame ID : 0
Subnode : 30
COM port : RS232
3.
Enter the ESCM configuration mode and query the default analog and digital parameters.
huawei(config)#
interface emu 0
huawei(config-if-MiniESC-0)#
display esc system parameter
EMU ID: 0 ESC system parameter
----------------------------------------------------------------------------
FAN run mode: Auto Auto open temperature: 45 C Auto close temperature: 30
C
AnalogID Name AlmUpper AlmLower TestHigh TestLow Unit type
0 Temperature 55 5 100 -27 C Voltage
1 Input_-48V_0 75 45 75 0 volt Voltage
2 - 127 -128 127 -128 - Voltage
3 - 127 -128 127 -128 - Voltage
----------------------------------------------------------------------------
DigitalID Name Available Level|DigitalID Name Available Level
0 Wiring 1 | 1 Door0 0
2 - 1 | 3 - 1
4 - 1 | 5 - 1
6 - 1 | 7 - 1
8 - 1 | 9 - 1
----------------------------------------------------------------------------
The results show that certain monitoring parameters, such as temperature, voltage, door
status, and MDF, have been configured automatically in the system. Other monitoring
parameters, however, need to be configured manually.
4.
Configure the analog parameters.
huawei(config-if-MiniESC-0)#
esc analog 0 alarm-upper-limit 50 alarm-lower-
limit 10
UA5000 Universal Access Unit
Environment Monitoring
5 ESCM Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
56