huawei(config-if-MiniESC-0)#
esc analog 2 alarm-upper-limit 80 alarm-lower-
limit 0 name Humidity sensor-type 0:voltage analog-alarm 2 unit %RH
5.
Configure the digital parameters.
huawei(config-if-MiniESC-0)#
esc digital 9 available-level low-level name szl9
digital-alarm 7
6.
Query the default configuration of the analog and digital parameters.
huawei(config-if-MiniESC-0)#
display esc environment info
EMU ID: 0 ESC environment state
FAN control mode :Auto FAN run state: Open
---------------------------Analog environment info--------------------------
ID Name State Value AlmUpper AlmLower Unit
0 Temperature Normal 29.00 50 10 C
1 Input_-48v_0 Normal 53.906 75 45 V
2 Humidity Normal -128.00 127 -128 -
3 - Normal -128.00 127 -128 -
---------------------------Digital environment
info---------------------------
ID Name State Value |ID Name State Value
0 Wiring Normal 1 |1 Door0 Alarm 1
2 - Normal 1 |3 - Normal 1
4 - Normal 1 |5 - Normal 1
6 - Normal 1 |7 - Normal 1
8 - Normal 1 |9 szl9 Normal 0
----------------------------------------------------------------------------
NOTE
The door status alarm "Door0" is generated because the door is open.
7.
Save the data.
huawei(config-if-MiniESC-0)#
quit
huawei(config)#
save
8.
Close all the cabinet doors. Query the environment information again, and confirm that no
door status alarm is generated.
UA5000 Universal Access Unit
Environment Monitoring
5 ESCM Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
57