Table 6-4
Indicators on the monitoring module of the EPS30-4815AF power system
Indicator
Status
Description
RUN
Green and blinking 1s on
and 1s off
The monitoring module functions properly.
Blinking green quickly
The monitoring module hardware is normal
but the communication between the
monitoring module and the upper device is
abnormal.
Off
The monitoring module is faulty or there is no
power input.
ALM
Steady red
The system generates a critical alarm or the
battery is disconnected.
Off
The system does not generate any critical
alarm and the battery is already connected.
Input Terminal
The EPS30-4815AF power system supports one 220 V AC power input and the standard 3-pin
connector is used.
shows the input terminals of the EPS30-4815AF power system.
Figure 6-2
Input terminals of the EPS30-4815AF power system
AC INPUT
RUN
ALM
AC INPUT
RUN
ALARM
FAULT
GERM4815T
GERM4815T
RUN
ALARM
FAULT
EPMU03
COM
RS232/RS485
FU-BT
20A
FU-1
10A
FU-2
20A
DC OUTPUT
LOAD1
10A
LOAD2
20A
BATT.
20A
Output Terminal
The EPS30-4815AF power system supports three output terminals. The two pins on the left of
the output terminal are the output positive pole and the two pins on the right of the output terminal
are the output negative pole.
shows the output terminals of the EPS30-4815AF power system.