Silk
Screen
Signal Port
Pin Function
VTEM2
Sensor port of
temperature and
humidity 2
l
Pin 1 is for the +24 V power supply.
l
Pin 2 is for the temperature signal cable.
The external sensor outputs the 4-20 mA current signal.
JTP1
Sensor port of the
MDF
l
Pin 1 is for the signal cable.
l
Pin 2 is reserved.
SMOKE
Smoke sensor port
l
Pin 1 is for the signal cable.
l
Pin 2 is for the +24 V power supply.
JTM1
Door-status sensor
port
l
Pin 1 is for the signal cable.
l
Pin 2 is for the +24 V power supply.
By default, when pin 1 and pin 2 are connected, the door
is in the normal state; when they are disconnected,
alarms are triggered. If no door-status sensor is used,
connect pin 1 and pin 2 to disable door-status alarms.
JK1, JK2
Alarm digital ports
The maximum voltage is 60 VDC and the maximum
load current is 500 mA.
l
When minor alarms are generated, JK2 is short-
circuited.
l
When critical alarms are generated, JK1 is short-
circuited.
l
Users can define alarm levels through the BAM
program.
JKM1-
JKM4
Digital ports
The maximum voltage is 5.6 VDC and the maximum
current is 20 mA.
SIM1,
SIM2
Battery unbalanced
sensor ports
l
Pin 1 is for the signal cable.
l
Pin 2 is reserved.
JAC1-
JAC6
Output ports of the
optical coupler
Pin 1 and pin 2 are connected to pole C and pole E of
the optical coupler.
The optical coupling parameter Vce max is 40 VDC and
Ic max is 80 mA. Avoid setting the parameters to the
maximum values.
FU_ALM
Detecting port of the
battery fuse
l
Pin 1 is for the signal cable FU1+ and is connected
to the negative pole of the battery.
l
Pin 2 is reserved for the FU1- signal.
UA5000 Universal Access Unit
Environment Monitoring
6 EPS30-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
67