Monitoring Parameter
Displayed on the Host
Device Port
Application in the M200 Cabinet
Digital 5
JTD6
Not connected by default, used to add
a user-defined monitoring digital
parameter
Digital 6
JTD7
Not connected by default, used to add
a user-defined monitoring digital
parameter
Door alarm
JTM1
Door status sensor
Wiring alarm
JTP1
MDF
Battery Tem
BAT_WE
Not connected by default, used to add
a user-defined monitoring digital
parameter
environment Tem/
environment Hum
TEM-HU
Temperature and humidity sensor
NOTE
Before adding a user-defined analog or monitoring digital parameter, make sure that the port corresponding
to this analog or monitoring digital parameter is properly connected with an environment monitoring cable.
Data Plan
provides the data plan for configuring the monitoring parameters of the
EPS30-4815AF.
Table 6-13
Data plan for configuring the monitoring parameters of the EPS30-4815AF
Item
Data Plan for the
F01E400 Cabinet
Remarks
EMU
Type: POWER4845
During the configuration of the EPS30-4815AF,
the type of the EPS30-4815AF is selected as
POWER4845
.
SN: 0
-
Subnode ID: 0
The subnode ID must be the same as the subnode
setting of the corresponding DIP switch on the
EMU, but the subnode ID must be different from
IDs of the other subnodes on the same bus.
UA5000 Universal Access Unit
Environment Monitoring
6 EPS30-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
71