Item
Data Plan for the
F01E400 Cabinet
Remarks
Number of battery sets:
1
This parameter is set according to the actual
requirements. The number of battery sets can be
set to 0 or 1. That is, the system supports up to one
battery set.
Default: 1.
Capacity of the battery
set: 75 AH
The battery capacity is configured according to
the actual value. The F01E200 cabinet uses the 50
AH batteries, the F01E400 cabinet uses the 75 AH
batteries, and the M200 cabinet has no batteries.
Default: 130 AH.
Temperature
compensatio
n parameters
of the battery
Upper temperature
threshold of the battery
set: 80°C
This parameter is set according to the actual
requirements.
Default: 60°C.
Lower temperature
threshold of the battery
set: -20°C
This parameter is set according to the actual
requirements.
Default: -40°C.
Temperature
compensation
coefficient of the battery
set: 80 mV
This parameter is set according to the actual
requirements. The temperature compensation
coefficient refers to the variable of the float
charging voltage of the battery set when the
temperature of the battery set changes by every 1°
C.
Default: 100 mV.
Power
supply load
power-off
and battery
set power-off
parameters
Load power-off
permission status: forbid
This parameter is set according to the actual
requirements.
Default: permit.
Battery set power-off
permission status:
permit
This parameter is set according to the actual
requirements.
Default: permit.
Load power-off voltage:
44 V
This parameter is set according to the actual
requirements.
Default: 43.5 V.
Battery set power-off
voltage: 43 V
This parameter is set according to the actual
requirements.
Default: 43 V.
UA5000 Universal Access Unit
Environment Monitoring
6 EPS30-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
73