load off permit : permit load off voltage : 43.500V
battery off permit : permit battery off voltage : 43.000V
shunt quotiety : 100A
AC over alarm voltage : 280V AC lack alarm voltage : 180V
DC over alarm voltage : 58 V DC lack alarm voltage : 45V
power module number: 3
module 0 address : 1 module 0 control state: On
module 1 address : 2 module 1 control state: On
module 2 address : No Configured module 2 control state: -
Load high-temperature-off permit: permit
Load high-temperature-off temperature(C): 65
Battery high-temperature-off permit: permit
Battery high-temperature-off temperature(C): 50
----------------------------------------------------------------------------
huawei(config-if-power4845-0)#display power environment parameter
EMU ID: 0 power environment configration
parameter
----------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestHigh TestLow Unit type
0 Temperature 50 0 55 -5 C
Current
1 Humidity 80 10 100 0 %R.H.
Current
----------------------------------------------------------------------------
DigitalID Name Available Level|DigitalID Name Available Level
0 - 1 | 1 - 1
2 - 1 | 3 - 1
4 - 1 | 5 - 1
6 - 1
----------------------------------------------------------------------------
The results show that the power, temperature, and humidity parameters have been
configured automatically in the system; however, certain parameters need to be modified,
and certain extended monitoring parameters need to be added.
4.
Configure the battery charging parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the
power charge
command.
5.
Configure the battery management parameters.
huawei(config-if-power4845-0)#
power battery parameter 0.15 60 1 75
6.
Configure the temperature compensation coefficient of the battery.
huawei(config-if-power4845-0)#
power battery temperature 80 -20 80
7.
Configure the power supply load power-off and battery set power-off parameters.
huawei(config-if-power4845-0)#
power off load-off-state forbid load-off-voltage
44
8.
Configure the power distribution parameters.
If the planned data is the same as the query result, the parameters need not be configured.
If the parameters need to be modified, run the
power supply-parameter
command.
9.
Configure the rectifier unit parameter.
huawei(config-if-power4845-0)#
power battery-test auto-discharge-permit 180 0 2
46
10. Configure the load and battery high-temperature power-off parameters.
huawei(config-if-power4845-0)#
power temperature-off load-off-state forbid
load-off-temperature 70 battery-off-state permit battery-off-temperature 53
11. Configure the environment parameters.
l
Configure the temperature parameters.
huawei(config-if-power4845-0)#
power environment temperature 68 -5 80 -20
UA5000 Universal Access Unit
Environment Monitoring
6 EPS30-4815AF Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
79