Table 7-16
Connections of environment monitoring cables in the F01D200 cabinet
Cable
One End Connects to...
The Other End Connects
to...
Monitoring cable
(2): EPS75-4815AF
(1): J1 port of the sensor
transfer box
Test and alarm cable
(3): STACK OUT port on
the HWCF transfer board
of the HABD shelf
l
(3.1): JTD1 port of the
sensor transfer box
l
(3.2-3.3): RS485/RS232
ports on the monitoring
unit of the
EPS75-4815AF
Monitoring cable of the surge
protector
Alarm terminal of the
surge protector
JTP3 port of the sensor
transfer box
Smoke sensor cable
Smoke sensor
JTP5 port of the sensor
transfer box
Monitoring cable of the heat
exchanger
Heat exchanger
JTP6 port of the sensor
transfer box
Door status sensor
communication cable
MDF compartment door
status sensor
JTP7 port of the sensor
transfer box
Monitoring cable of the MDF
Alarm bar of the MDF
JTP1 port of the sensor
transfer box
Door status sensor
communication cable
Equipment compartment
and temperature control
compartment door status
sensor
JTM1 port of the sensor
transfer box
Monitoring cable of the
temperature and humidity sensor
Temperature and humidity
sensor
TEM-HU terminal of the
sensor transfer box
Monitoring cable of the battery
temperature sensor
Temperature sensor of the
battery
BAT_WE terminal of the
sensor transfer box
Checking Environment Monitoring Cables in the F01D500 Cabinet
shows the connections of environment monitoring cables in the F01D500 cabinet.
describes the cable connections. By referring to the cable connection diagram, check
whether the connections from the sensors to the sensor transfer box, from the sensor transfer
box to the EPMU02T, and from the EPMU02T to the control system are correct.