NOTE
By default, the ETP4890 power system is installed with a monitoring module, which is capable of the
inband management, the COM port can not be used as a network port.
Indicators
describes the indicators on the rectifier module of the ETP4890 power system.
Table 8-4
Indicators on the rectifier module of the ETP4890 power system
Indicator
Color
Status
Description
Power indicator
Green
Steady on
Normal
Blinking
There is AC input,
and the PSU is in the
manual query status
Off
No AC input
Alarm indicator
Yellow
Steady on
A protection
mechanism is
triggered. After the
fault is rectified, the
rectifier module can
be restored to the
normal state
Blinking
Communication
between the PSU and
the SMU is disrupted
Off
Normal
Fault indicator
Red
Steady on
An unrecoverable
fault occurs
Blinking
Software is being
loaded
Off
Normal
describes the indicators on themonitoring module.
Table 8-5
Indicators on the monitoring module
Indicator
Color
Status
Description
RUN
Green
Off
The monitoring
module is faulty or
there is no DC power
input
UA5000 Universal Access Unit
Environment Monitoring
8 ETP4890 Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
124