Silk Screen
Signal Port
Pin Function
VTEM2
Port for detecting temperature 2
l
Pin 1 is for the +12 V power
supply.
l
Pin 2 is for the signal cable.
JTD1-JTD7
Port for digital parameter input
l
Pin 1 and pin 2 are for +12 V
power supply.
l
Pin 3 is for the signal cable.
l
Pin 4 is for grounding.
SMOKE
Smoke sensor port
l
Pin 1 is for the signal cable.
l
Pin 2 is for +12 V power supply.
WATER
Water sensor port
l
Pin 1 is for +12 V power supply.
l
Pin 2 is for the signal cable.
l
Pin 3 is for grounding.
JTM1
Door status sensor port
l
Pin 1 is for the signal cable.
l
Pin 2 is for +12 V power supply.
JTP1
Sensor port on the MDF
l
Pin 1 is for the signal cable.
l
Pin 2 is reserved.
JK1/JK2
Alarm dry contact output port
The maximum voltage is 60 V DC
and the maximum load current is
500 mA.
JAC1/JAC2
Alarm dry contact output port
The maximum voltage is 60 V DC
and the maximum load current is
500 mA.
JKM1-JKM4
Alarm dry contact output port
The maximum voltage is 60 V DC
and the maximum load current is
500 mA.
CAB_E-LABEL
Cabinet electronic label port
l
Pin 1 is for +5 V power supply.
l
Pin 2 is for the clock cable.
l
Pin 3 is for the digital cable.
l
Pin 4 is for grounding.
Parameter
lists the specifications of the MUE02A sensor transfer box.
Table 8-9
Specifications of the MUE02A sensor transfer box
Parameter
Specifications
Dimensions (H x W x D)
31 mm x 140 mm x 96 mm
UA5000 Universal Access Unit
Environment Monitoring
8 ETP4890 Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
130