Table 5-3
Settings of SW1
Electrical
Switch
Setting
Indication
Factory Default
SW1-1 to
SW1-4
Supported
Used to set the address of the
environment monitoring board.
SW1-1: ON
SW1-2: ON
SW1-3: OFF
SW1-4: OFF
SW1-5
Not
supported
-
ON
SW1-6
ON
The rate of the serial port is 19200
bit/s.
OFF
OFF
The rate of the serial port is 9600 bit/
s.
SW1-7
ON
The external sensor of JTA1 is of the
current type.
ON
OFF
The external sensor of JTA1 is of the
voltage type.
SW1-8
ON
The external sensor of JTA2 is of the
current type.
ON
OFF
The external sensor of JTA2 is of the
voltage type.
When the ESCM EMU adopts the RS-485 communication mode, SW1-1 to SW1-4 are used to
set the address of the environment monitoring board.
shows the settings of SW1-1 to
SW1-4.
Table 5-4
Settings of SW1-1 to SW1-4
SW1-4
SW1-3
SW1-2
SW1-1
Address Value
0
0
0
0
0
0
0
0
1
1
0
0
1
0
2
0
0
1
1
3
0
1
0
0
4
0
1
0
1
5
0
1
1
0
6
0
1
1
1
7
UA5000 Universal Access Unit
Environment Monitoring
5 ESCM Monitoring Solution
Issue 01 (2012-08-17)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
49