UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
A Alarm Handling
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
98
Alarm
Name
Alarm
ID
Alarm
Cause
ID
Alarm
level
Alarm
Clear Mode
Impact on the
System
Repair Proposal
ECO
voltage
exception
60
1
Minor
Automatic
clear
The UPS cannot
transfer to ECO
mode. If the UPS is
working in bypass
mode, it transfers to
another working
mode.
Possible cause: The ECO
input is abnormal.
Measure: Check whether
the ECO input voltage or
frequency is out of the
specified range. If the
voltage or frequency is
out of the specified
range, change the range
setting or wait for the
bypass input to recover.
Bypass
mode
9E
1
Minor
Automatic
clear
If the bypass is
abnormal, the UPS
may shut down.
Possible cause: The
inverter is not started.
Measure: Check
whether other alarms
are generated. If other
alarms are generated,
handle these alarms
according to the
handling methods.
Possible cause: The
load exceeds the
rated loading capacity
of the inverter.
Measure: If other
alarms are not
generated, manually
start the UPS.
Possible cause: The
inverter is faulty.
Measure: Contact
Huawei technical
support.
Battery
mode
9F
1
Minor
Automatic
clear
If batteries are
abnormal, the UPS
may shut down.
Possible cause: The
mains input is
abnormal.
Measure: Check the
mains input. If the
mains input is
abnormal, wait for
the mains to recover.
Possible cause: The
battery self-check is
in progress.
Measure: Check
whether the battery