UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
3 Installation
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
31
Figure 3-4
Cable routes for a rack-mounted UPS
(1) AC output
power cable
(2) AC input
power cable
(3) Cable between the UPS
and the battery pack
(4) Cable between the
battery packs
3.2.3 Connecting Cables
Prerequisites
Ensure that the L and N wires of UPS AC input and output power cables are connected
correctly. Ensure that battery terminals are connected correctly.
Before connecting cables, ensure that the input circuit breaker, external output circuit
breaker (if any), and battery circuit breaker are OFF to avoid operations with power on.
Procedure
Step 1
Turn off the AC input circuit breaker on the rear of the UPS, external output circuit breaker (if
any), and battery circuit breaker.
Step 2
Remove the cover of the AC input, output, and battery wiring terminals from the UPS.