UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
4 Control Panel
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
55
Name
Screen
Function
Value
Range
Preset
Value
Remarks
Upper
voltage
threshold
Upper threshold
for the ECO
voltage. In ECO
mode, when the
difference between
the bypass voltage
and the rated
output voltage
exceeds this value,
the system
determines that the
ECO voltage is
abnormal and
transfers to normal
mode.
5%, 6%,
7%, 8%,
9%, and
10%
10%
The value is
configurable
only after the
inverter shuts
down.
Lower
voltage
threshold
Lower threshold
for the ECO
voltage. In ECO
mode, when the
difference between
the bypass voltage
and the rated
output voltage
exceeds this value,
the system
determines that the
ECO voltage is
abnormal and
transfers to normal
mode.
5%, 6%,
7%, 8%,
9%, and
10%
10%
The value is
configurable
only after the
inverter shuts
down.