UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
62
Step 8
Set the charge current limit. The default value for the 6 kVA/10 kVA UPS with long backup
time is 2 A. The value range is 1 A to 12 A with an interval of 0.5 A. Set this parameter based
on the actual situation.
Figure 5-6
Setting the charge current limit
Step 9
Start the UPS to work in normal mode by using one of the following methods.
On the default screen, hold down
for more than 5 seconds. Release the button
when you hear a beep sound. If the UPS starts successfully, it enters normal mode, as
shown in
Figure 5-7
Normal mode
On the standby screen, hold down
to enter the
CTR
menu. Select
INV ON
in the
CTR
menu. If the UPS starts successfully, it enters normal mode, as shown in
Figure 5-8
Normal mode