On the default screen, hold down
for more than 5 seconds. Release the button
when you hear a beep sound. If the UPS starts successfully, it enters normal mode, as
shown in
Figure 5-15
Battery mode
On the standby screen, hold down
to enter the
CTR
menu. Select
INV ON
in the
CTR
menu. If the UPS starts successfully, it enters normal mode, as shown in
Figure 5-16
Battery mode
Step 10
After checking that the system is running properly, turn on the load switch to start the load.
To prevent triggering overload protection, start the loads with higher power and then loads with lower
power.
----End
5.2.2 Shutting Down the UPS
Shutting Down the Inverter to Transfer the UPS to Bypass Mode
To shut down the inverter, perform any of the following operations:
On the default screen, hold down ESC for more than 5 seconds. Release the button when
you hear a beep sound. The inverter shuts down, and the UPS transfers to bypass mode.