UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
9 Technical Specifications
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
79
Item
6 kVA/10 kVA
Rated input voltage
220 V AC, 230 V AC, or 240 V AC
Input voltage
80–280 V AC (When the voltage is 80–176 V AC, the
load power is linearly derated to 40%–100%.)
Input frequency
45–55 Hz/55–65 Hz
Input power factor (100% load)
> 0.99
No-load loss
6 kVA: < 54 W
10 kVA: < 90 W
Startup voltage
120–280 V AC
Diesel
Minimum: 1.5 times the UPS rated capacity
9.4 Bypass Input Electrical Specifications
Item
6 kVA/10 kVA
Bypass voltage range
Upper threshold: 10%, 15%, 20%, or 25% at 220 V
AC
Upper threshold: 10%, 15%, or 20% at 230 V AC
Upper threshold: 10%, or 15% at 240 V AC
Lower threshold: 10%, 20%, 30%, 40%, 50%, or 60%
Bypass frequency range
Maximum ±5 Hz
Bypass overload capability
Load < 125%: The UPS continuously works. The
input circuit breaker may trip in advance.
125% ≤ load < 150%: The UPS stops power output
after 1 minute. The input circuit breaker may trip in
advance.
Load ≥ 150%: The UPS stops power output after 200
ms. The input circuit breaker may trip in advance
(load is calculated based on the bypass currents).
Input mode
Single mains
9.5 Output Electrical Specifications
Item
6 kVA/10 kVA
Rated capacity
6 kVA/10 kVA