UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
9 Technical Specifications
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
80
Item
6 kVA/10 kVA
Output power factor
0.9 (When the power factor ranges from 0.5 to 1, the
UPS2000-A with inductive load is not derated. When
the power factor ranges from 0.5 to 1, the UPS2000-A
with 80%–100% capacitive load is linearly derated.)
Rated output voltage
220 V AC/230 V AC/240 V AC (selected by setting a
voltage level on the LCD.)
Output voltage precision
±1%
Total harmonic distortion of the
output voltage waveform (THDv)
≤ 5% (configured with a residual current device
(RCD) with a 0.7 power factor, and specified in
the IEC62040 standards of THDv.)
≤ 2% (resistive load. Each harmonic meets the
limit specified by the IEC62040.)
Crest factor
A maximum of 3:1
Overload capacity
Normal mode, 105%–125% load: The UPS
transfers to bypass mode in 5 minutes if the bypass
is normal or disconnects the output if the bypass is
abnormal.
Normal mode, 125%–150% load: The UPS
transfers to bypass mode in 1 minute if the bypass
is normal or disconnects the output if the bypass is
abnormal.
Normal mode, ≥ 150% load: The UPS transfers to
bypass mode in 0.2 second if the bypass is normal
or disconnects the output if the bypass is
abnormal.
Dynamic voltage transient
±5%
Average frequency tracking rate
0.5–2 Hz/s for a single UPS
9.6 Battery Electrical Specifications
Item
6 kVA/10 kVA
Rated battery voltage
192–240 V DC
Number of batteries
12 V lead-acid batteries; a long backup time model
connects to external battery packs with 16–20
batteries configured.
Leakage current
≤ 500 µA
Power backup time
Determined by the battery capacity.
For the power backup time of the battery pack
for the 6 kVA UPS, see