UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
A Alarm Handling
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
87
Alarm
Name
Alarm
ID
Alarm
Cause
ID
Alarm
level
Alarm
Clear Mode
Impact on the
System
Repair Proposal
timeout
l
clear/Power-
off clear
down.
bypass loading
capacity exceeds the
rated load of the
inverter.
Measure: Reduce the
output load, manually
clear the alarm, and
restart the UPS.
Possible cause: An
internal fault has
occurred.
Measure: Contact
Huawei technical
support.
Batt.
reverse
14
1
Critica
l
Automatic
clear
This alarm does not
affect the UPS or
the power supply.
Possible cause: The
positive and negative
battery terminals are
reversely connected.
Measure: Check the
battery installation, and
install batteries again.
No battery
16
1
Minor
Automatic
clear
This alarm does not
affect the power
supply.
Possible cause: No
batteries are
connected.
Measure: Connect
batteries.
Possible cause: The
batteries are in poor
contact.
Measure: Check the
battery cable
connection. If battery
cables are loose,
connect them
securely.
Battery
overtemper
ature
17
1
Minor
Automatic
clear
An alarm is
generated, and the
battery lifespan is
affected.
Possible cause: The
temperature inside the
UPS or the ambient
temperature exceeds the
battery overtemperature
alarm threshold (default
value: 50º
C).
Measure: Reduce the
ambient temperature and
keep the air intake and
exhaust vents of the UPS