UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
A Alarm Handling
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
88
Alarm
Name
Alarm
ID
Alarm
Cause
ID
Alarm
level
Alarm
Clear Mode
Impact on the
System
Repair Proposal
unblocked.
Battery
overvoltage
19
1
Minor
Automatic
clear
An alarm is
generated, and the
battery lifespan is
affected.
Possible cause: The
battery voltage
reaches the alarm
threshold due to
continuous charge.
Measure: When
batteries are in charge
mode, wait for 2
minutes and check
whether the alarm is
cleared.
Possible cause: The
number of batteries
configured is less
than the actual
number of batteries.
Measure: Check
whether the number
of batteries is
correctly set.
Battery low
voltage
1A
1
Minor
Automatic
clear
An alarm is
generated, and the
system may shut
down due to EOD.
Possible cause: The
mains is abnormal, and
the batteries are
overdischarged.
Measure: Connect to the
mains in non-battery test
state.
Battery
overvoltage
protection
20
1
Critica
l
Automatic
clear
An alarm is
generated, and the
battery lifespan is
affected.
Possible cause: The
number of batteries
configured is less
than the actual
number of batteries.
Measure: Check that
the configured
number of batteries is
consistent with the
actual number.
Possible cause: The
actual number of
batteries does not
meet requirements.
Measure: Check that
the actual number of
batteries meets
requirements.