UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
A Alarm Handling
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
89
Alarm
Name
Alarm
ID
Alarm
Cause
ID
Alarm
level
Alarm
Clear Mode
Impact on the
System
Repair Proposal
Possible cause: The
charger is abnormal.
Measure: Check that
the charger voltage is
normal immediately
after the batteries are
disconnected.
Remaining
cap.
warning
22
1
Minor
Automatic
clear
If no action is taken,
continued discharge
will result in system
shutdown due to
EOD.
Possible cause: The
battery discharge
lasts too long.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
mains input is
abnormal.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
number of batteries
or battery capacity is
incorrectly set.
Measure: Check the
configured battery
capacity.
Battery
overcurrent
1B
1
Minor
Automatic
clear
An alarm is
generated, and the
battery lifespan is
affected.
Possible cause: The
charger is abnormal.
Measure: Contact
Huawei technical
support.
Battery
maintenanc
e required
1D
1
Minor
Manual clear
The battery backup
time is affected.
Possible cause: The
battery capacity is
incorrectly
configured.
Measure: Check that
the configured battery
capacity is consistent
with the actual
battery capacity.
Possible cause: The
battery circuit cannot
discharge currents.
Measure: Check the