UPS2000-A-(6 kVA-10 kVA)
User Manual
B Alarm Handling
Issue 04 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
141
Alarm
Name
Alar
m
Ident
ifier
(Alar
m ID)
Web
UI
Deci
mal
Syste
m
Alarm
Identi
fier
(Alar
m ID)
LCD
Heuri
sticim
al
Syste
m
Alarm
level
Alarm
Clear
Mode
Impact on the
System
Repair Proposal
ff clear mode.
Possible cause: The parallel cables
are damaged.
Measure: Replace the parallel
cables.
Parallel
cable
alarm
54-2
84-2
Minor
Autom
atic
clear
This alarm has
no adverse
impact.
Possible cause: The parallel cables
connected are loose.
Measure: Check that parallel cables
are securely connected.
Possible cause: The parallel cables
are damaged.
Measure: Replace the parallel
cables.
Parallel
cable
alarm
54-3
84-3
Minor
Autom
atic
clear
This alarm has
no adverse
impact.
Possible cause: The parallel cables
connected are loose.
Measure: Check that parallel cables
are securely connected.
Possible cause: The parallel cables
are damaged.
Measure: Replace the parallel
cables.
EPO
55-1
85-1
Critical
Manua
l
clear/P
ower-o
ff clear
The UPS shuts
down.
Possible cause: You have pressed the
EPO switch.
Measure: Restore the EPO switch
status, clear the alarm, and restart the
UPS.
Bypass
transfer
times
limit
56-1
86-1
Minor
Manua
l
clear/P
ower-o
ff clear
The UPS cannot
transfer to an
unsteady side.
Possible cause: The output is
transferred more than three times
within 30 minutes.
Measure: Clear the alarm and restart
the UPS.
Insufficie
nt
redundan
cy
5E-1
94-1
Minor
Autom
atic
clear
This alarm has
no adverse
impact.
Possible cause: The number of
redundant UPSs is too large.
Measure: Reduce the number of
redundant UPSs or set the UPS to