UPS2000-A-(6 kVA-10 kVA)
User Manual
5 Operations
Issue 04 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
92
Figure 5-35
Transferring from single mode to parallel mode
Step 11
Start each UPS in the parallel system one by one by using either of the following methods for
the parallel system to work in battery mode:
After you perform "startup operations" on UPS 1 to UPS
n
one by one, UPS 1 to UPS
n
are starting. If
you do not perform "startup operations" on the other UPSs in 3 minutes, UPS 1 to UPS
n
enter normal
mode, and the other UPSs supply no power.
On the default screen, hold down
for more than 5 seconds. Release the button
when you hear a beep sound. If the UPS starts successfully, it enters battery mode, as
shown in Figure 5-36.
Figure 5-36
Battery mode
On the default screen, hold down
to enter the
CTR
menu. Select
INV ON
in the
CTR
menu. If the UPS starts successfully, it enters battery mode, as shown in Figure