UPS2000-A-(6 kVA-10 kVA)
User Manual
5 Operations
Issue 04 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
93
Figure 5-37
Battery mode
Step 12
After you ensure that the parallel system runs properly, switch on the AC output circuit
breaker of the parallel system to supply power to the loads.
To prevent triggering overload protection, start the loads with higher power and then loads with lower
power.
----End
5.3.2 Shutting Down the Parallel System
Shutting Down the Inverter to Transfer to Bypass Mode
Shut down the UPS using either of the following methods:
On the default screen, hold down
ESC
for about 5s. Release the button when you hear a
beep sound. The inverter shuts down, and the UPS transfers to bypass mode.
On the default screen, press
to enter the
CTR
menu. Choose
INV OFF
to shut
down the inverter. The UPS transfers to bypass mode, as shown in Figure 5-38.