UPS2000-A-(6 kVA-10 kVA)
User Manual
5 Operations
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
107
When a UPS works in normal mode, do not switch on the maintenance bypass circuit
breaker of the parallel system.
If you need to maintain a UPS, transfer all UPSs to bypass mode and then switch on the
maintenance bypass circuit breaker of the parallel system.
This topic uses the UPS professional version with long backup time as an example to illustrate
how to connect maintenance bypass cables, as shown in
. A UPS of the
professional version has embedded batteries and therefore does not require battery cables.
Figure 5-45
Connecting maintenance bypass cables
(1) AC input circuit breaker of
UPS 1
(2) AC input circuit
breaker of UPS 2
(3) AC output circuit
breaker of UPS 1