UPS2000-A-(6 kVA-10 kVA)
User Manual
5 Operations
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
109
Step 8
Set parameters and start the system. If there is more than one UPS.
Step 9
Check whether the new parallel system is working properly. If yes, shut down the system and
switch on the AC output circuit breaker of the parallel system.
Step 10
Switch off the maintenance bypass circuit breaker of the parallel system and start the system.
----End