9.2 Environmental Specifications
Item
6 kVA/10 kVA
Standard
Version with
Standard
Backup Time
6 kVA/10
kVA
Standard
Version with
Long Backup
Time
6 kVA/10
kVA
Professional
Version with
Standard
Backup Time
6 kVA/10
kVA
Professional
Version with
Long Backup
Time
Operating
temperature
0–40°C
Humidity
0%–95% RH (non–condensing)
Altitude
< 1000 meters
When the altitude is 1000–4000 meters, see IEC62040–3 to check how
the UPS power is derated. (When the altitude increase 100 m, the
output power derated 1%.)
Storage and
transportation
temperature
–20°C to +40°C
–40°C to
+70°C
–20°C to
+40°C
–40°C to
+70°C
9.3 Mains Input Electrical Specifications
Item
6 kVA/10 kVA
Standard
Version with
Standard
Backup Time
6 kVA/10 kVA
Standard
Version with
Long Backup
Time
6 kVA/10 kVA
Professional
Version with
Standard
Backup Time
6 kVA/10 kVA
Professional
Version with
Long Backup
Time
Input
power
cable
Single-phase
(L/N) input +
PE cable
Single-phase
(L/N) input + PE
cable
Single-phase
(L/N) input +
PE cable
Dual-live-wire
(L1 and L2)
input + PE
cable
Single-phase
(L/N) input +
PE cable
Dual-live-wire
(L1 and L2)
input + PE
cable
Rated
input
voltage
220 V AC, 230
V AC, or 240 V
AC
220 V AC, 230 V
AC, or 240 V AC
208 V AC, 220 V
AC, 230 V AC,
or 240 V AC
208 V AC, 220 V
AC, 230 V AC,
or 240 V AC
Input
voltage
80–280 V AC (When the voltage is 80–176 V AC, the load power is linearly
derated to 40%-100%.)
Input
frequenc
y
45–55 Hz/55–65 Hz
Input
> 0.99