UPS2000-A-(6 kVA-10 kVA)
User Manual
2 Overview
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
24
Component
Model
Function
Remarks
remote
monitoring.
6 kVA output
isolation
transformer
box
DGL-6/0.22
Provides isolation
solutions for customer
equipment. Compared
with the output
transformer on an
industrial frequency
UPS, the output
transformer box
provides isolation
functions even in
bypass mode. The
isolation transformer is
a 2:1:1
industrial-frequency
transformer. It converts
one 220 V output
voltage into two
isolated 110 V outputs.
The output
isolation
transformer box
is 6 kVA,
single-phase. It is
used for the
UPS2000-A-6
kVA.
10 kVA output
isolation
transformer
box
DGL-10/0.22
The output
isolation
transformer box
is 10 kVA,
single-phase. It is
used for the
UPS2000-A-10
kVA.
Standard
battery box (7
Ah, 20
batteries)
ESS-240V12-2*7AhBPV
BA
Consists of two strings
of twenty 12 V, 7 Ah
lead-acid batteries
connected in series. It is
a standard configuration
for the 6 kVA UPS. A
maximum of two
battery boxes can be
connected in parallel.
A UPS with
standard backup
time does not
support external
battery boxes. A
UPS with long
backup time can
be configured
with one or two
external battery
boxes.
Standard
battery box (9
Ah, 20
batteries)
ESS-240V12-2*9AhBPV
BA
Consists of two strings
of twenty 12 V, 9 Ah
lead-acid batteries
connected in series. It is
a standard configuration
for the 10 kVA UPS. A
maximum of two
battery boxes can be
connected in parallel.
Modbus card
RMS-MODBUS01A
Provides two cascaded
RJ45 ports to
implement networking
over the Modbus or
YDN-23 protocol.
N/A
Dry contact
card
RMS-RELAY01A
Provides six alarm dry
contact outputs (normal
mode, battery mode,
bypass mode, low
battery voltage, bypass
backfeed, and UPS
faults) and two dry
N/A