UPS2000-A-(6 kVA-10 kVA)
User Manual
3 Installation
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
53
Figure 3-26
Bypass backfeed protection connections for the UPS2000-A-6 kVA/10 kVA
(dual-live-wire)
3.5 Check After Installation
lists check items after installation.
Table 3-6
Post-installation check items
No.
Item
Expected Result
1
Cable routing
Cable routing meets engineering
requirements.
2
Cable connections
Power cables and battery cables are
tightened to specified torques using a torque
wrench, connected correctly, and free of
damage.
3
Cable connections for USB ports
and network ports
Cables to USB ports and network ports are
connected correctly and securely.
4
Cable labels
Labels are neatly attached to both ends of
each cable, and the information on the labels
is concise and understandable.
5
Ground cable connection
The ground cable is securely connected to
the equipment room ground bar. Measure
the resistance between the UPS ground