4 Control Panel
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
73
Na
me
LCD
Function
Value
Range
Preset
Value
Remarks
Tot
al
batt
ery
cap
acit
y
Set the
battery
capacity.
(The
battery
capacity is
the total
capacity of
battery
strings and
is set based
on the
actual
capacity.)
7–999 Ah
6 kVA
with
standar
d
backup
time: 7
Ah
10 kVA
with
standar
d
backup
time: 9
Ah
6 kVA
with
long
backup
time:
40 Ah
10 kVA
with
long
backup
time:
65 Ah
The value
is
configura
ble in
non-batter
y mode or
non-batter
y ECO
mode.
Cha
rge
curr
ent
limi
t
Maximum
charge
current in
equalized
charge
mode. The
interval is
0.5 A.
1.0–8.0 A
6 kVA
with
standar
d
backup
time:
2.0 A
(unconf
igurable
)
10 kVA
with
standar
d
backup
time:
2.0 A
(unconf
igurable
)
6 kVA
with
long
The
parameter
is
configura
ble in any
mode.