5 Operations
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
84
Step 7
(This step is required only for the UPS with long backup time.) Set the battery capacity to the
total capacity of all batteries actually connected. The default value is 40 Ah for the 6 kVA
UPS with long backup time. The default value is 65 Ah for the 10 kVA UPS with long
backup time, and the value can range from 7 Ah to 999 Ah.
Figure 5-5
Setting the battery capacity
Step 8
(This step is required only for the UPS with long backup time.) Set the charge current limit
based on actual conditions. The default value is 4.0 A for the UPS with long backup time, and
the value can range from 1.0 A to 8.0 A, the interval is 0.5 A.
Figure 5-6
Setting the charge current limit
Step 9
Start the UPS to work in normal mode by using one of the following methods.
On the default screen, hold down
for more than 5 seconds. Release the button
when you hear a beep sound. If the UPS starts successfully, it enters normal mode, as
shown in
Figure 5-7
Normal mode
On the standby screen, hold down
to enter the
CTR
menu. Select
INV ON
in the
CTR
menu. If the UPS starts successfully, it enters normal mode, as shown in