UPS2000-A-(6 kVA-10 kVA)
User Manual
3 Installation
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
32
Model
Wiring
Terminal
Rated
Voltage
External
Circuit
Breaker
Cross-
sectional
Area
Terminal
Type
Torque for
Tightening
Bolts
backup
time
AC
(feature
D)
10 kVA
standard
version
with
long
backup
time
Input
220 V
AC, 230
V AC, or
240 V
AC
63 A
(feature
D)
10 mm
2
OT-10
mm
2
-M6
terminal
2.8 N.m
Output
63 A
(feature
D)
Battery
240 V
DC
63 A
10 mm
2
lists the recommended power cable specifications for the UPS professional version.
Table 3-3
Recommended power cable specifications for the UPS professional version
Model
Wiring
Termin
al
Rated
Voltage
External
Circuit
Breaker
ELCB Cross-se
ctional
Area
Termi
nal
Type
Torqu
e for
Tighte
ning
Bolts
6 kVA
professional
version with
standard
backup time
Input
208 V
AC, 220
V AC,
230 V
AC, or
240 V
AC
50 A
(feature
D)
100
mA
6 mm
2
OT-6
mm
2
-
M4
termin
al
1.4
N.m
Output
50 A
(feature
D)
N/A
6 kVA
professional
version with
long backup
time
Input
208 V
AC, 220
V AC,
230 V
AC, or
240 V
AC
50 A
(feature
D)
100
mA
6 mm
2
OT-6
mm
2
-
M4
termin
al
1.4
N.m
Output
50 A
(feature
D)
N/A
Battery
240 V
DC
50 A
N/A
6 mm
2
10 kVA
professional
version with
standard
backup time
Input
208 V
AC, 220
V AC,
230 V
AC, or
240 V
AC
63 A
(feature
D)
100
mA
10 mm
2
OT-10
mm
2
-
M6
termin
al
2.8
N.m
Output
63 A
(feature
D)
N/A