UPS2000-G-(6 kVA-20 kVA)
User Manual
B LCD Menus and Parameters
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
108
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
after the
inverter shuts
down)
Shutdown
delay
0–600 seconds
0S
Shallow
Discharge
Test
notification
Enabled and Disabled
Disabled
Time interval
30–90 days
60 Day
Discharge ratio
10%–50%
20%
Settings
wizard
(configur
able after
the
inverter
shuts
down)
Language
N/A
English, Chinese,
Spanish, French, and
Russian
English
System
Parameters
Voltage level
220 V, 230 V, and
240 V (on the
UPS2000-G-6
kVA/10 kVA)
220 V, 230 V, and
240 V, single-phase
(on the
UPS2000-G-15
kVA/20 kVA)
380 V, 400 V, and
415 V, three-phase
(on the
UPS2000-G-15
kVA/20 kVA)
220 V (on the
UPS2000-G-6
kVA/10 kVA)
220 V, single-phase
(on the
UPS2000-G-15
kVA/20 kVA)
380 V, three-phase
(on the
UPS2000-G-15
kVA/20 kVA)
Frequency
level
50 Hz, 60 Hz, and
Automatic
50 Hz
Output mode
(configurable
only on the
UPS2000-G-15
kVA/20 kVA)
Single-phase and
Three-phase
Three-phase (on the
UPS2000-G-15 kVA/20
kVA)
Battery
Parameters
Batteries
/Positive
batteries/Negati
ve batteries
16–20 monoblocs
20 Monobloc
Battery
capacity
7–1000 Ah
For the UPS2000-G-6
kVA, the default
value is
7 Ah
on a
standard model and
40
Ah
on a long backup
time model.