UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
116
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
batt.
c clear
affected.
The battery capacity is
incorrectly set.
The battery loop cannot be
discharged.
The battery capacity is low.
Measures:
Check whether the configured
battery capacity matches the
connected battery capacity.
Check battery connections
and the status of each battery.
Contact Huawei technical
support for repair.
0030-01
UPS
inter
overtemp
.
Minor
Automati
c clear
The power supply from the
UPS and system is not
affected.
Possible causes:
The ambient temperature
exceeds 40°C.
The air channel is blocked.
The fan is abnormal.
Measures:
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the UPS
unobstructed.
Clean off the foreign objects
around the fan. If the alarm
persists, contact Huawei
technical support for repair.
0032-01
Batt.
OVP
Critical
Automati
c clear
An alarm is generated, and
the battery lifespan is
affected.
Possible causes:
The configured number of
batteries is less than the actual
number.
The actual number of batteries
does not meet specifications.
The charger is abnormal.
Measures:
Check that the configured
number of batteries matches
the actual number.
Check that the actual number