UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
118
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
Measures:
After you rectify the fault,
restart the UPS.
Contact Huawei technical
support for repair.
0040-04
Rectifier
fault
Critical
Manual
clear/Po
wer-off
clear/Aut
omatic
clear
The UPS shuts down.
The UPS transfers to
another working mode or
shuts down.
Possible causes:
The mains experiences
instantaneous high-voltage
impact.
The output has special loads
such as inductive loads and
rectification loads.
The output has transformer
loads but the transformer
mode is not set.
The hardware is damaged.
Measures:
After you rectify the fault,
restart the UPS.
Check whether the load type
is supported by the UPS.
Enable the transformer mode.
Contact Huawei technical
support for repair.
0040-05
Rectifier
fault
Critical
Manual
clear/Po
wer-off
clear/Aut
omatic
clear
The UPS shuts down.
The UPS transfers to
another working mode or
shuts down.
Possible cause: The hardware is
damaged.
Measure: Contact Huawei
technical support for repair.
0040-06
Rectifier
fault
Critical
Power-of
f clear
The UPS shuts down.
The UPS transfers to
another working mode or
shuts down.
Possible cause: The hardware is
damaged.
Measure: Contact Huawei
technical support for repair.
0040-07
Rectifier
fault
Critical
Automati
c clear
The UPS shuts down.
The UPS transfers to
another working mode or
shuts down.
The charger stops
working.
Possible causes:
The ambient temperature
exceeds 40°C.
The air channel is blocked.
The fan is abnormal.