UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
123
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
0049-01
Battery
qty.
wrong
Minor
Manual
clear/Po
wer-off
clear/Aut
omatic
clear
An alarm is displayed, and
the battery service life may
be shortened.
Possible causes:
The number of batteries is
incorrectly set.
Batteries are damaged.
If batteries are fully charged,
reconnect the batteries as soon
as the system powers off.
Measures:
Check whether the number of
batteries is correctly set.
Check whether batteries are
damaged.
After ensuring that the
number of batteries is correct,
clear the alarm.
0060-01
Inverter
fault
Critical
Power-of
f clear
The inverter shuts down.
The UPS transfers to
bypass mode or has no
output based on the
transfer logic.
Possible cause: The inverter is
faulty.
Measure: Contact Huawei
technical support for repair.
0060-02
Inverter
fault
Critical
Power-of
f clear
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible cause: The inverter relay
is faulty.
Measure: Contact Huawei
technical support for repair.
0060-03
Inverter
fault
Critical
Power-of
f clear
0060-04
Inverter
fault
Critical
Power-of
f clear
Possible cause: The inverter
output is short-circuited.
Measure: Rectify output port
short circuits. After you clear the
alarm, restart the UPS. If the
alarm persists, contact Huawei
technical support for repair.
0060-05
Inverter
fault
Critical
Automati
c clear
Possible causes:
The mains experiences
instantaneous high-voltage
impact.
The output has special loads
such as sensitive loads and
rectification loads.
The output has transformer
loads but the transformer