UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
124
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
mode is not set.
The hardware is faulty.
Measures:
After you rectify the fault,
restart the UPS.
Check whether the load type
is supported by the UPS.
Enable the transformer mode.
Contact Huawei technical
support for repair.
0060-07
Inverter
fault
Critical
Automati
c clear
The UPS starts upon
shutdown.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
The ambient temperature
exceeds 40º
C.
The air channel is blocked.
The fan is abnormal.
Measures:
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the UPS
unobstructed.
Clean off the foreign objects
around the fan. If the alarm
persists, contact Huawei
technical support for repair.
0060-08
Inverter
fault
Critical
Manual
clear/Po
wer-off
clear
The UPS shuts down.
Possible cause: The DSP or
CPLD chip is faulty.
Measure: Contact Huawei
technical support for repair.
0061-01
Inverter
alarm
Minor
Manual
clear/Po
wer-off
clear/Aut
omatic
clear
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible causes:
Parallel cables are incorrectly
connected.
The lengths of parallel cables
vary greatly.
Measures:
Reconnect cables.
The lengths of parallel cables
vary within a range of 5%.