128
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
paral.
param.
c clear
all the UPSs in the parallel
system cannot start
inverters.
parameters are not set
consistently on the UPSs.
Measure: Set the parallel
parameters consistently, or
perform parallel parameter
synchronization.
NOTE
After you perform parallel parameter
synchronization, contact Huawei
technical support if some parallel
parameters are still inconsistent.
0131-01
Ambient
overtemp
erature
Minor
Automati
c clear
An alarm is generated.
Possible causes:
The ambient temperature in
the UPS equipment room
exceeds the alarm threshold
(default value: 40°C).
The temperature and humidity
transducer is faulty.
Measures:
Check the ambient
temperature in the UPS
equipment room.
Replace the temperature and
humidity transducer.
0133-01
Ambient
undertem
perature
Minor
Possible causes:
The ambient temperature in
the UPS equipment room is
below the alarm threshold
(default value: 0º
C).
The temperature and humidity
transducer is faulty.
Measures:
Check the ambient
temperature in the UPS
equipment room.
Replace the temperature and
humidity transducer.
0134-01
Ambient
overhum
idity
Minor
Possible causes:
The ambient humidity in the
UPS equipment room exceeds
the alarm threshold (default
value: 90%).