UPS2000-G-(6 kVA-20 kVA)
User Manual
C Alarm Handling
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
129
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
The temperature and humidity
transducer is faulty.
Measures:
Check the ambient humidity
of the UPS equipment room.
Replace the temperature and
humidity transducer.
0135-01
Ambient
underhu
midity
Minor
Possible causes:
The ambient humidity in the
UPS equipment room is
below the alarm threshold
(default value: 10%).
The temperature and humidity
transducer is faulty.
Measures:
Check the ambient humidity
of the UPS equipment room.
Replace the temperature and
humidity transducer.
0136-01
Faulty
temperat
ure and
humidity
module
Minor
Possible causes: The temperature
and humidity module is faulty.
Measures:
Check parameter settings of
the temperature and humidity
transducer.
Replace the temperature and
humidity transducer.
0158-01
On
bypass
Minor
Automati
c clear
If the bypass is abnormal,
the UPS may power off.
Possible causes:
The inverter is not started.
The load exceeds the rated
inverter loading capacity.
The inverter is faulty.
Measures:
Check whether other alarms
are generated. If yes, see the
other handling methods.
If no, start the UPS manually.
0159-01
On
battery
Minor
Automati
c clear
The UPS may power off if
batteries are abnormal.
Possible causes:
The mains input is abnormal.