UPS2000-G-(6 kVA-20 kVA)
User Manual
3 Installation
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
27
Model
Wirin
g
Termi
nal
Num
ber
of
Phas
es
Rated
Voltage
Externa
l
Circuit
Breaker
Cross-s
ectional
Area
Termin
al Type
Torqu
e for
Tighte
ning
Bolts
Output
1
220 V AC,
230 V AC,
or 240 V
AC
100 A
(the
characte
ristics of
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8
N·m
15 kVA
(three-phas
e input
three-phase
output)
Bypass
input
3
380 V AC,
400 V AC,
or 415 V
AC
50 A
(the
characte
ristics of
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8
N·m
Mains
input
3
Battery
N/A
±240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8
N·m
Output
3
380 V AC,
400 V AC,
or 415 V
AC
50 A
(the
characte
ristics of
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8
N·m
20 kVA
(single-pha
se input
single-phas
e output)
One
mains
input
1
220 V AC,
230 V AC,
or 240 V
AC
125 A
(the
characte
ristics of
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8
N·m
Battery
NA
±240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8
N·m
Output
1
220 V AC,
230 V AC,
or 240 V
AC
125 A
(the
characte
ristics of
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8
N·m
20 kVA
(three-phas
e input
single-phas
e output)
Bypass
input
1
220 V AC,
230 V AC,
or 240 V
AC
125 A
(the
characte
ristics of
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8
N·m
Mains
input
3
380 V AC,
400 V AC,
or 415 V
AC
63 A
(the
characte
ristics of
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8
N·m