UPS2000-G-(6 kVA-20 kVA)
User Manual
3 Installation
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
28
Model
Wirin
g
Termi
nal
Num
ber
of
Phas
es
Rated
Voltage
Externa
l
Circuit
Breaker
Cross-s
ectional
Area
Termin
al Type
Torqu
e for
Tighte
ning
Bolts
Battery
N/A
±240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8
N·m
Output
1
220 V AC,
230 V AC,
or 240 V
AC
125 A
(the
characte
ristics of
D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8
N·m
20 kVA
(three-phas
e input
three-phase
output)
Bypass
input
3
380 V AC,
400 V AC,
or 415 V
AC
63 A
(the
characte
ristics of
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8
N·m
Mains
input
3
Battery
N/A
±240 V DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8
N·m
Output
3
380 V AC,
400 V AC,
or 415 V
AC
63 A
(the
characte
ristics of
D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8
N·m
If customers purchase input and output power cables by themselves, use the cables that comply with
standards proposed by Underwriters Laboratories (UL) or International Electrotechnical
Commission (IEC).
Two-mains-input scenarios are not supported on the UPS2000-G-15 kVA/20 kVA (single-phase
input single-phase output).