4 Control Panel
Issue 13 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
56
The frequency range must be less than the current bypass frequency range. The
values include ±0.5 Hz, ±1 Hz, ±2 Hz (default), and ±3 Hz. The parameter is
configurable after the inverter shuts down.
−
Single UPS ECO
parameter
Determine whether to support ECO mode on a single UPS (ECO mode is not
supported in a parallel system). The values include
Disabled
and
Enabled
. The
default value is
Disabled
. The parameter is configurable after the inverter shuts
down.
Power Segment
screen
Figure 4-34
Power Segment screen
In single UPS mode, primary loads connect to sL, and secondary loads connect to pL.
In single UPS mode, if power segment is enabled, pL is disconnected and sL continues with power
output when an overload occurs.
In a parallel system, UPS AC output power cables connect to pL.
−
Dis. time. thres.
parameter
pL terminal loading time in battery mode when power segment (not supported in a
parallel system) is enabled. In battery mode, if the discharge time exceeds this value,
the UPS disconnects from secondary loads. The value ranges from 0 Min to 999
Min, in units of minutes. The default value is 30 Min. The parameter is configurable
in non-battery mode or non-battery ECO mode.
The UPS2000-G-15 kVA/20 kVA supports battery ECO mode only in the case of two mains inputs. In
battery ECO mode, the bypass supplies power to the UPS, and batteries are used as backup power. If the
bypass is abnormal, the UPS transfers to battery mode.
−
Dis. volt. thres.
parameter
Set the lower threshold for the battery voltage when pL loading is allowed in battery
mode when power segment (not supported in a parallel system) is enabled. In
battery mode, if the battery voltage is less than this value, the UPS disconnects from
secondary loads. The value ranges from 1.90 V/cell to 2.25 V/cell. The default
value is 2.00 V/cell. The parameter is configurable in non-battery mode or
non-battery ECO mode
−
Power segment
parameter
Determine whether to enable power segment in singe UPS mode (power segment is
not supported in a parallel system). The values include
Disabled
and
Enabled
. The
default value is
Disable
d. The parameter is configurable after the inverter shuts
down.
Self-Load
screen